Files
Conflict_Checker/backend/.llm_cache/3cd1fab325af7f4d28a3610366fc74c9a29a0ce4dae25ab6fbd398603f725a1b.json
T
woogiandClaude Opus 4.8 1d248a8808 Initial commit: Conflict Checker
Cross-discipline design-contradiction checker for construction drawing
sets. Standalone tool broken out from Iron_Bid; a pipeline stage may
later fold back into Iron_Bid.

Pipeline: PDF->images -> per-sheet assertion extraction -> deterministic
clustering by location -> per-cluster reasoning -> report.
Includes CLI (cli/run_check.py) and web UI (backend/main.py).

Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
2026-07-03 00:22:02 +00:00

1 line
1.2 KiB
JSON

{"conflicts": [{"conflict_id": "inv_rack_data_conduit_quantity", "category": "note_or_spec_contradiction", "severity": "medium", "confidence": "high", "location": "INVENTORY room, network rack", "disciplines": ["Architectural", "Electrical"], "sheets": ["A24.01", "E02.01"], "description": "The Architectural drawing specifies a requirement for three 3-inch conduits for data cabling at the network rack. The Electrical drawing shows both the required three 3-inch conduits (as sleeves) and an additional, separate 1-1/4 inch conduit for data. The total scope and quantity of data pathways is inconsistent between the drawings and must be clarified.", "evidence": [{"discipline": "Architectural", "sheet": "A24.01", "source_text": "PROVIDE (3) 3\" CONDUITS FROM DIRECTLY ABOVE THE NETWORK RACK INTO THE SALES CEILING PLENUM AREA FOR DATA CABLING - FIELD COORDINATE.", "asserted_value": "(3) 3-inch conduits"}, {"discipline": "Electrical", "sheet": "E02.01", "source_text": "3 PROVIDE 1-1/4\"C WITH PULLSTRING FOR DATA TO CEILING SPACE ABOVE RACK SYSTEM IN INVENTORY ROOM... 6 FURNISH AND INSTALL (3) 3\" CONDUIT SLEEVES... FOR DATA EQUIPMENT WIRING.", "asserted_value": "(3) 3-inch conduits AND (1) 1-1/4 inch conduit"}], "recommended_resolution": "coordinate drawings"}]}