{"issues": [{"issue_id": "VER-ELY-P02.01-001", "source_stage": "code", "category": "ada", "severity": "high", "confidence": "high", "location": "Women's Restroom", "disciplines": ["Plumbing", "Architectural"], "sheets": ["P02.01"], "description": "The plans indicate the only drinking fountain (EDF-1) is located inside the Women's Restroom. This denies access to drinking water for male occupants and any person unable to use the Women's Restroom, which does not provide equitable access to building amenities.", "evidence": [{"discipline": "Plumbing", "sheet": "P02.01", "source_text": "EDF-1", "asserted_value": "EDF-1 is located in WOMEN'S ROOM."}], "recommended_resolution": "Relocate the drinking fountain to a common use area accessible to all occupants, such as the Sales Area or a corridor. If only one fountain is provided, it must be a hi-lo unit to serve both standing persons and wheelchair users.", "code_reference": null}, {"issue_id": "VER-ELY-P03.01-001", "source_stage": "code", "category": "building_code", "severity": "low", "confidence": "high", "location": "Pipe Penetration Detail", "disciplines": ["Plumbing", "Architectural"], "sheets": ["P03.01"], "description": "A detail note on sheet P03.01 cites the '2021 IBC, CHAPTER 19, SECTION 1907' for a vapor retarder requirement. The project's adopted building code is the 2015 IBC. All code references on the drawings should align with the applicable code for the jurisdiction.", "evidence": [{"discipline": "Plumbing", "sheet": "P03.01", "source_text": "PER 2021 IBC, CHAPTER 19, SECTION 1907: POLYETHYLENE VAPOR RETARDER MINIMUM 6-MIL SHALL BE REQUIRED.", "asserted_value": "Vapor retarder detail cites 2021 IBC."}], "recommended_resolution": "Verify the vapor retarder requirement under the 2015 IBC and update the code citation on the drawing.", "code_reference": null}, {"issue_id": "VER-ELY-P03.01-002", "source_stage": "code", "category": "building_code", "severity": "medium", "confidence": "medium", "location": "Water Heater EWH-1", "disciplines": ["Plumbing"], "sheets": ["P02.02", "P03.01"], "description": "The Temperature and Pressure (T&P) relief valve drain line for water heater EWH-1 is routed from the unit's location above the ceiling to a floor sink below. Plumbing codes typically require the T&P discharge point to be readily observable to serve as a visual safety indicator of malfunction. Routing the drain through a concealed space before discharge may not meet this requirement's intent.", "evidence": [{"discipline": "Plumbing", "sheet": "P03.01", "source_text": "A.S.M.E. RATED TEMP. AND PRESSURE RELIEF VALVE. PIPE DISCHARGE 3/4\" TO FLOOR SINK PER PLANS", "asserted_value": "Pipe discharge 3/4\" to floor sink per plans"}, {"discipline": "Plumbing", "sheet": "P02.02", "source_text": "KEYED NOTE: 1 EWH-1 ABOVE CEILING SUSPENDED AS HIGH AS POSSIBLE IN CEILING PLENUM. PROVIDE AUXILIARY DRAIN PAN BELOW WATER HEATER...", "asserted_value": "EWH-1 is located above ceiling, suspended as high as possible in ceiling plenum and requires an auxiliary drain pan."}], "recommended_resolution": "Verify with the Authority Having Jurisdiction (Harris County) that this T&P drain termination method is acceptable. The International Plumbing Code generally requires the discharge to be visible.", "code_reference": null}]}