{"conflicts": [{"conflict_id": "EHW1_voltage_mismatch", "category": "schedule_vs_plan_mismatch", "severity": "high", "confidence": "high", "location": "Electric Water Heater EWH-1 and Electrical Panel 'E'", "disciplines": ["Plumbing", "Electrical"], "sheets": ["P01.01", "E01.02"], "description": "The Electric Water Heater Schedule on P01.01 specifies a 480V, 3-phase unit for EWH-1. The Electrical drawings on E01.02 show the 'WATER HEATING' load connected to Panel 'E', which is a 208Y/120V panel. The specified equipment is incompatible with the provided power source, which will lead to procurement and installation failure.", "evidence": [{"discipline": "Plumbing", "sheet": "P01.01", "source_text": "EWH-1 | VOLTS 480 | PHASE 3", "asserted_value": "480V, 3-Phase"}, {"discipline": "Electrical", "sheet": "E01.02", "source_text": "PANEL NAME: E | MAINS 100.0 | VOLTS 208Y/120 | PHASE 3 WIRE 4W ... DESCRIPTION: WATER HEATING", "asserted_value": "208Y/120V"}], "recommended_resolution": "coordinate drawings"}]}