{"conflicts": [{"conflict_id": "rtu_curb_height_discrepancy_01", "category": "note_or_spec_contradiction", "severity": "medium", "confidence": "high", "location": "Roof Curb for new RTUs at Grid B-C/4-5", "disciplines": ["Architectural", "Mechanical"], "sheets": ["M01.01", "A25.01"], "description": "The mechanical schedule on M01.01 specifies a 14-inch high roof curb for the new RTUs. The architectural roof curb detail on A25.01 contains conflicting information: one note states '14\" HIGH PER IECC & MFR'S REQ.' which is consistent, but another note in the same detail says to 'Nominate 1'0\"' (12 inches). This ambiguity will cause confusion for bidding and installation, potentially impacting waterproofing and structural coordination.", "evidence": [{"discipline": "Mechanical", "sheet": "M01.01", "source_text": "9. PROVIDE 14\" HIGH INSULATED ROOF CURB.", "asserted_value": "14 inches"}, {"discipline": "Architectural", "sheet": "A25.01", "source_text": "Nominate 1'0\" for P.Con.", "asserted_value": "12 inches"}], "recommended_resolution": "coordinate drawings"}]}